Permit Number: T09CM02651
Parcel: 13424436A

Address:
6301 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T09CM02651
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2009 ANDREW CONNOR LANDSCAPE REVIEW Approved
11/10/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The copy of the appeal to the building official submitted with these plans cannot be recognized until after it has been approved by the building official. Original comment: Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited. (A 6" ABS building drain, flowing half full at a slope of 1.5%, and an 8" ABS building drain, flowing half full at aslope of 1%, will convey approximately 785 GPM. A 4" ABS drain, flowing full at a slope of 1% can only handle about 85 GPM.) Reference: Section 316.4.1, UPC 2006.
11/12/2009 JASON GREEN ENGINEERING REVIEW Approved
11/16/2009 RONALD BROWN ZONING HC REVIEW Approved
11/19/2009 TERRY STEVENS ZONING REVIEW Approved