Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T09CM02651
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2009 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 11/10/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The copy of the appeal to the building official submitted with these plans cannot be recognized until after it has been approved by the building official. Original comment: Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited. (A 6" ABS building drain, flowing half full at a slope of 1.5%, and an 8" ABS building drain, flowing half full at aslope of 1%, will convey approximately 785 GPM. A 4" ABS drain, flowing full at a slope of 1% can only handle about 85 GPM.) Reference: Section 316.4.1, UPC 2006. |
| 11/12/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/16/2009 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
| 11/19/2009 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/23/2009 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 11/23/2009 | SUE REEVES | REJECT SHELF | Completed |