Permit Number: T09CM02647
Parcel: 14042023D

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM02647
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2009 DAVE MANN FIRE REVIEW Approved
10/06/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 6950 S Country Club Rd.
T09CM02647
Parking Canopy Solar Panels,

The Electrical Plans for this project have been denied for the following:
1. Sheet E1.2, The #6 THWN-2 GRD (GRN) shown going from the Existing Switchgear needs to classifiedas a neutral.
This being defined as a service , it is required to have a neutral per 2005 NEC 250-24, up to the Main Disconnect for the Photo Voltaic system.
2. Provide notation on Electrical Plans , that labels are required and to be placed on electrical equpment as per 2005 NEC Article 690 following Sections-----

690.7(D)
690-14(C)(2)
690-17
690-53
690-54
705.22, and any others as required per 2005 NEC.





Ray T Majuta
Elect Pln Ck
PDSD City of Tucson
10/07/09
Ray.Majuta@tucsonaz.gov
10/07/2009 SREEVES1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
10/08/2009 SUE REEVES REJECT SHELF Completed