Permit Number: T09CM02632
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02632
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 8: PROVIDE A REFERENCE ON DETAIL C/A10.2 TO THE SPECIFIC STRUCTURAL SECTION ON SHEET S01.1.
2. PREVIOUS COMMENT 10: DID NOT LOCATE THE ANGLE BRACE SIZE OR CONNECTION DETAIL ON SHEET S01.1. AS REFERENCED ON DETAIL S/A10.3. PROVIDE.
3. PREVIOUS COMMENT 11: PROVIDE A REFERENCE ON DETAIL A/A11.1 TO THE SPECIFIC STRUCTURAL SECTION ON SHEET S01.1.
4. PREVIOUS COMMENT 12: PROVIDE A REFERENCE ON DETAIL A/A11.1a TO THE SPECIFIC STRUCTURAL SECTION ON SHEET S01.1.
5. PREVIOUS COMMENT 13: PROVIDE A REFERENCE ON DETAILS A/A11.2 AND E/A11.2 TO THE SPECIFIC STRUCTURAL SECTION ON SHEET S01.1.
6. PREVIOUS COMMENT 14: PROVIDE A REFERENCE ON DETAIL A/A11.5 TO THE SPECIFIC STRUCTURAL SECTION ON SHEET S01.1.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/13/2009 MARTIN BROWN FIRE REVIEW Approved
11/16/2009 GERRY KOZIOL WWM REVIEW Approved
11/17/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
11/24/2009 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/24/2009 CPIERCE1 WATER REVIEW Approved
11/24/2009 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Approved Comment not resolved. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
11/24/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
11/24/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
11/24/2009 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.