Permit Number: T09CM02626
Parcel: 117030170

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02626
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2009 DAVE MANN FIRE REVIEW Approved
10/05/2009 RONALD BROWN ZONING HC REVIEW Denied What are you doing to make this building more accessible?
10/05/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S2.1; BEAM SCHEDULE: WHERE IS BEAM B1 LOCATED ON THE PLAN? VERIFY.
2. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR ALL ROOF BEAMS AND COLUMNS AND FOR THE FLOOR BEAMS.
3. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR ANY NEW OR EXISTING FOOTINGS/FOUNDATIONS SUPPORTING NEW LOADS.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/05/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S2.1; BEAM SCHEDULE: WHERE IS BEAM B1 LOCATED ON THE PLAN? VERIFY.
2. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR ALL ROOF BEAMS AND COLUMNS AND FOR THE FLOOR BEAMS.
3. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR ANY NEW OR EXISTING FOOTINGS/FOUNDATIONS SUPPORTING NEW LOADS.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/08/2009 GERRY KOZIOL WWM REVIEW Approved
10/14/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the static lift in the water pressure calculations to correspond to the actual conditions (approximately 22 feet of lift). Reference: 610.1, UPC 2006.
2. One of the specified fixtures (American Standard Cadet water closet - 25 PSIG) requires a minimum pressure greater than the 15-PSI used in the water pipe sizing calculations. Revise calculations as necessary. Reference: Section 608.1, UPC 2006.
3. The water pressure appears to be insufficient to provide the minimum required residual water pressure. Show how the water distribution system will be revised to provide the required residual water pressure. Reference: Section 608.1, UPC 2006.
4. The water heater appears to be located under the extended eave of the roof. Provide the manufacturer's instructions that allow this type of installation. Reference: Section 510.2.6, UPC 2006.
10/14/2009 ROBERT SHERRY WATER REVIEW Approved
10/14/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the method of support and the weights for the two evaporative coolers with the structural engineer. Reference: Sections 106.3.1 and 302.1, IMC 2006.
2. Provide guards for the rooftop equipment located within 10'-0" of the roof edge. Reference: Section 304.10, IMC 2006.
3. Show how ventilation will be provided to the dormitory area during the heating season. Reference: Section 401.2, IMC 2006.
10/22/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/26/2009 TERRY STEVENS ZONING REVIEW Denied 10/26/2009

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2009 DELMA ROBEY OUT TO CUSTOMER Completed