Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02626
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/05/2009 | RONALD BROWN | ZONING HC | REVIEW | Denied | What are you doing to make this building more accessible? |
| 10/05/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S2.1; BEAM SCHEDULE: WHERE IS BEAM B1 LOCATED ON THE PLAN? VERIFY. 2. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR ALL ROOF BEAMS AND COLUMNS AND FOR THE FLOOR BEAMS. 3. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR ANY NEW OR EXISTING FOOTINGS/FOUNDATIONS SUPPORTING NEW LOADS. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/05/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S2.1; BEAM SCHEDULE: WHERE IS BEAM B1 LOCATED ON THE PLAN? VERIFY. 2. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR ALL ROOF BEAMS AND COLUMNS AND FOR THE FLOOR BEAMS. 3. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR ANY NEW OR EXISTING FOOTINGS/FOUNDATIONS SUPPORTING NEW LOADS. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/08/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/14/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the static lift in the water pressure calculations to correspond to the actual conditions (approximately 22 feet of lift). Reference: 610.1, UPC 2006. 2. One of the specified fixtures (American Standard Cadet water closet - 25 PSIG) requires a minimum pressure greater than the 15-PSI used in the water pipe sizing calculations. Revise calculations as necessary. Reference: Section 608.1, UPC 2006. 3. The water pressure appears to be insufficient to provide the minimum required residual water pressure. Show how the water distribution system will be revised to provide the required residual water pressure. Reference: Section 608.1, UPC 2006. 4. The water heater appears to be located under the extended eave of the roof. Provide the manufacturer's instructions that allow this type of installation. Reference: Section 510.2.6, UPC 2006. |
| 10/14/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/14/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the method of support and the weights for the two evaporative coolers with the structural engineer. Reference: Sections 106.3.1 and 302.1, IMC 2006. 2. Provide guards for the rooftop equipment located within 10'-0" of the roof edge. Reference: Section 304.10, IMC 2006. 3. Show how ventilation will be provided to the dormitory area during the heating season. Reference: Section 401.2, IMC 2006. |
| 10/22/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/26/2009 | TERRY STEVENS | ZONING | REVIEW | Denied | 10/26/2009 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/10/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |