Permit Number: T09CM02619
Parcel: 113052570

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02619
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2009 MARTIN BROWN FIRE REVIEW Approved
10/02/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide the specifications for the flexible ducts and the required insulation R-value.
10/02/2009 ERIC NEWCOMB ADA REVIEW Passed
10/02/2009 ROBERT SHERRY WATER REVIEW Approved
10/02/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE TWO SETS OF DRAWINGS FOR REVIEW.
2. SHEET DT1 (DETAIL 1): ADD VERTICAL GRAB BAR PER ANSI FIGURE 604.5.1.
3. SHEET DT1 (DETAIL 8): SHOW DRINKING FOUNTAIN AS SINGLE POINT-OF-USE.
10/02/2009 GERRY KOZIOL WWM REVIEW Approved
10/02/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. All lettering shall be at least 3/32" high.
2. Provide justification for the use of a flat vent for the water closets.
3. Show how the temperature of the hot water for the lavatories will be limited to 110 degrees Fahrenheit.
4. Provide a design for the water heater support and provide structural calculations to show that it will be safely attached to the wall.
5. Provide a vacuum relief for the water heater.
6. Provide insulation for the hot water piping.
7. Show the location of the plumbing fixtures on the plumbing floor plan.
10/02/2009 JASON GREEN ENGINEERING REVIEW Approved
10/02/2009 TERRY STEVENS ZONING REVIEW Approved
10/02/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
10/02/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/16/2009 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review