| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/29/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/02/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide the specifications for the flexible ducts and the required insulation R-value. |
| 10/02/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 10/02/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/02/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: PROVIDE TWO SETS OF DRAWINGS FOR REVIEW. 2. SHEET DT1 (DETAIL 1): ADD VERTICAL GRAB BAR PER ANSI FIGURE 604.5.1. 3. SHEET DT1 (DETAIL 8): SHOW DRINKING FOUNTAIN AS SINGLE POINT-OF-USE. |
| 10/02/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/02/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. All lettering shall be at least 3/32" high. 2. Provide justification for the use of a flat vent for the water closets. 3. Show how the temperature of the hot water for the lavatories will be limited to 110 degrees Fahrenheit. 4. Provide a design for the water heater support and provide structural calculations to show that it will be safely attached to the wall. 5. Provide a vacuum relief for the water heater. 6. Provide insulation for the hot water piping. 7. Show the location of the plumbing fixtures on the plumbing floor plan. |
| 10/02/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 10/02/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/02/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 10/02/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/16/2009 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |