Permit Number: T09CM02607
Parcel: 13316021D

Address:
6616 E GRANT RD

Review Status: Completed

Review Details: MODULAR BUILDINGS

Permit Number - T09CM02607
Review Name: MODULAR BUILDINGS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed
09/25/2009 STEVE SHIELDS ZONING REVIEW Approved
09/25/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/25/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/25/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
09/28/2009 DAVE MANN FIRE REVIEW Approved
09/28/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved Project: T09CM02607
6616 E. Grant RD

Denied for The Following:

1. Show location of service on plans

2. Provide one line diagram of service include the following:
- size of service
- grounding electrode system size and type
- conductor sizes include wiring method to trailer.

Rich Jiroudek 954-0161
Electric plns examining