Permit Number: T09CM02600
Parcel: 134270010

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02600
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project T09cm02600 , AT$T Cell site
1. The new drawing noe shows a 50 kva transformer, 277/480v to 120/240v. The feed to the transformer shows 3 phase, the transformer uses only 1 phase. Please correct this.

Ray T Majuta
DPDS<CIty of Tucson
Elect Plan Ck
11/17/09
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2009 SUE REEVES APPROVAL SHELF Completed
11/25/2009 CPIERCE1 OUT TO CUSTOMER Completed