Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM02600
Parcel: 134270010

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T09CM02600
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2009 DAVE MANN FIRE REVIEW Approved
09/30/2009 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Approved
09/30/2009 Michael Wyneken PLANNING-CITY HALL REVIEW Approved
10/08/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond Need to provide completed special inspection form for approval.
10/21/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 7600 E Broadway Bl, T09CM0600
AT&T Cell Tower on Roof of Hilton

The Electrical plans for this project have been denied for the following:

1. The official address that is required on the application will need to be "7600 E Broadway Bl. AT&T #1" since 7600 E Broadway Bl is used for the Hilton. If there are any other AT&T services on the building they must be in numerical order.
2. The AIC (available interruping current) at the service is shown to be 65,000 amps(Sheet 11),the Panel POPB is listed at 22,000amps AIC. How does the Fault Current breakdown to this figure, provide fault current calculations from service to the panel.(2005 NEC 110.9, 110.22)
3. The grounding system for the new service needs to comply with NEC 2005 250.58, because there are more than one service on the building.How will this be done.
4. Provide notation on plan that this service to to have a label stating that this service provides power only to the AT&T Cell Tower on the roof.

Ray T Majuta,
PDSD City of Tucson,
Elect Plan CK
10/21/09
Ray.Majuta@tucsonaz.gov
10/22/2009 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2009 THAUSER1 OUT TO CUSTOMER Completed
10/30/2009 SUE REEVES REJECT SHELF Completed