Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02587
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/26/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/27/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/27/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/28/2009 | SUE REEVES | APPROVAL SHELF | Completed |
| 10/28/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |