Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02584
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/24/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 09/24/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/24/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/24/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/24/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/24/2009 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 09/24/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 09/24/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 09/24/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/24/2009 | RONALD BROWN | ADA | REVIEW | Passed | |
| 09/24/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/24/2009 | RONALD BROWN | ZONING HC | REVIEW | Approved |