Permit Number: T09CM02583
Parcel: 125076370

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02583
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2009 MARTIN BROWN FIRE REVIEW Approved
10/01/2009 JASON GREEN ENGINEERING REVIEW Approved
10/01/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
10/01/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/01/2009 RONALD BROWN ZONING HC REVIEW Approved
10/01/2009 DAVID RIVERA ZONING REVIEW Approved
10/01/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/06/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise operation for the restroom exhaust to prevent recirculation of the air from the restroom during occupied hours. Reference: Section 403.2.1, IMC 2006.
2. Show that the opeation of the emulsifier (K1) will not violate the requirements of section 1201.3, IMC 2006, as amended by the city of Tucson.
11/06/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
11/06/2009 ROBERT SHERRY WATER REVIEW Denied Clarify the pressure drop associated with the 2" meter; Tucson Water limits the meters to a connected demand of 80 GPM (approximately 2 PSI drop). How many fixture units are connected to the meter?
11/06/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The specified dual check valve (Watts 7C) is not listed for the applications shown on the drawings. Revise the backflow protection per Section 603, UPC 2006. Reference: Table 6-2, UPC 2006.
11/18/2009 CAGUILA1 WWM REVIEW Needs Review