Permit Number: T09CM02579
Parcel: 117051000

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02579
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
09/23/2009 LOREN MAKUS ENGINEERING REVIEW Approved
09/29/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Lighting circuits on Panel C are overloaded according to their alotted wattages.All lighting circuits on Panels A and C. RTMajuta 9/29/09
09/29/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the new cooling units are justified per Section 503.2.2, IECC 2006.
09/29/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/29/2009 ROBERT SHERRY WATER REVIEW Approved
09/29/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/29/2009 MARTIN BROWN FIRE REVIEW Approved
09/29/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated project
09/29/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/29/2009 RONALD BROWN ZONING HC REVIEW Approved
09/30/2009 CAGUILA1 WWM REVIEW Needs Review