Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02579
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/23/2009 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/29/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Lighting circuits on Panel C are overloaded according to their alotted wattages.All lighting circuits on Panels A and C. RTMajuta 9/29/09 |
| 09/29/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show that the new cooling units are justified per Section 503.2.2, IECC 2006. |
| 09/29/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/29/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/29/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/29/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/29/2009 | RONALD BROWN | ADA | REVIEW | Passed | Not a COT owned/operated project |
| 09/29/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/29/2009 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
| 09/30/2009 | CAGUILA1 | WWM | REVIEW | Needs Review |