Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02557
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/21/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 09/21/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/21/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/21/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 09/22/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/22/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/22/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/22/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/22/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/22/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/22/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A maximum of 8 fixture units is allowed on a 2" horizontal drain. Reference: section 703.2, UPC 2006. 2. Provide the height and offset for the new flue. Reference: 511.0, UPC 2006. |