Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM02555
Parcel: 112062340

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02555
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2009 STEVE SHIELDS ZONING REVIEW Approved
09/21/2009 LOREN MAKUS ENGINEERING REVIEW Approved
09/21/2009 ERIC NEWCOMB ADA REVIEW Passed
09/21/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/21/2009 ERIC NEWCOMB ZONING HC REVIEW Passed
09/21/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/22/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/22/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09cm02555
2516 N. Campbell Av

This project denied for the following reasons:

1. Need to show new electric in new walls. Include circuit numbers and load.

2. Need to show circuiting for new water heater. Include circuit numbers and load.

3. Need to show panel include the following;
- Rating of existing panel, feeder size, panel overcurrent protection
- Panel directory
- Load on panel include existing and new loads.

Rich Jiroudek 954-0161
Electric Plns Examining
09/22/2009 ROBERT SHERRY WATER REVIEW Approved
09/22/2009 DAVE MANN FIRE REVIEW Approved
09/22/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/24/2009 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/24/2009 DELMA ROBEY OUT TO CUSTOMER Completed