Permit Number: T09CM02481
Parcel: 11460011J

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02481
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2009 GERRY KOZIOL WWM REVIEW Approved
10/07/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM02481

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007; the 2006 UPC with amendments on 7/10/2007; effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation. All new SFR and duplex plans should reference these codes. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes ; Building Codes

GENERAL NOTES:

" Limit all code references to those recognized by the City of Tucson. Revise the Inclusive Home Design notation showing 2006 (exterior accessible route) and electrical thermostat height 48" (electrical third line).
" Interior alterations require the installation of smoke alarms at existing bedrooms, R313.2.1.

SITE PLAN:

1. Show the water meter and water pipe size between the meter and point of connection for new plumbing, R106.1.1.
2. Show or notate protection of footing when trenching parallel to the building. Trenching shall not extend below the 45-degree load-bearing plane from the bottom edge of the footing, IRC 2604.4.

SECTIONS - DETAILS:

1. Provide roof sheathing thickness Keynote #3 sheet A1 and Keynote #2 sheet A2, R106.1.1.
2. Provide consistent roof rafter sizes at Keynote #3 sheet A1 & Keynote #2 sheet A2 and the Framing Plan sheet A4 & Keynote #9 sheet A5, R106.1.1.
3. Specify all ledgers connected to masonry walls with 3x material at Detail b/A4 and Keynote #8 sheet A5, R606.11.

PLUMBING PLANS:

1. The plans may reference one code 2006 UPC or 2006 IRC for the Plumbing design. Revise General Note #1 or 4. Water fixture schedules may reference IRC P2903.6.
2. Provide a revised fixture unit schedule showing fixture values for the future water and drain lines to the Spa area, UPC 610.8, Table 6-6 or IRC P2903.6. The drain may be used for a shower, but not a discharge for the spa. The water service line may require upgrading for supporting a future shower.

ELECTRICAL PLANS:

1. Revise the electrical riser diagram showing the sub-panel feeder conductor sized for 60A, E3303. The 60A panel lugs will not receive 4/0 cable. The 200A panel schedule correctly shows #6 feeder conductor for the sub-panel.
2. Revise the sub-panel schedule showing the exterior receptacle on circuit #5 (adjacent to panel), E3304.11 & E3606.2.
3. Specify recessed lighting with 3" separation from combustibles or IC listing, R808, and compliance with energy efficiency leakage, N1102.4.3.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2009 CPIERCE1 OUT TO CUSTOMER Completed
10/13/2009 SUE REEVES REJECT SHELF Completed