Permit Number: T09CM02461
Parcel: 113060300

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM02461
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE MATERIAL SPECIFICATIONS ON THE PLANS, INCLUDING CONCRETE, REINFORCING STEEL, TIMBER, GLUE LAMINATED TIMBER, COLD FORMED STEEL, AND MIKEY BLOCK.
2. SHEET 3 OF THE DRAWINGS; BUILDING SECTION: PROVIDE SECTIONS AND DETAILS OF THE MIKEY BLOCK ON THE DRAWINGS, INCLUDING TYPICAL WALL REINFORCEMENT SIZE AND SPACING AND LINTEL SIZE AND REINFORCEMENT.
3. SHEET 3 OF THE DRAWINGS: ADD A NOTE TO THE DRAWING INDICATING THE CONNECTION OF THE METAL ROOF DECK TO THE ROOF FRAMING AT THE COVERED PORCHES.
4. CALCULATION PAGE 9: UNDER THE SOIL DATA, THE ALLOWABLE SOIL BEARING IS LISTED AS 1500 PSF, WHILE THE CALCULATION PAGE 1 LISTS 1000 PSF. CLARIFY. ON PAGE 9 DESIGN SUMMARY, THE SOIL PRESSURE AT THE FOOTING TOE AND HEEL BOTH EXCEED THE 1000 PSF ALLOWABLE PRESSURE.
5. GENERAL: PROVIDE LATERAL CALCULATIONS FOR THE ROOF DIAPHRAGM. ADD ROOF DIAPHRAGM CONNECTION REQUIREMENTS TO THE DRAWINGS.