Permit Number: T09CM02457
Parcel: 128040630

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02457
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 12-08-09
Activity: T09CM02457
Address: 5711 e North Wilshire
Applicant: James Kearney

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FLOOR PLANS:
3. Specify safety glazing in hazardous locations, R308.4. Within 24" of doorways

PLUMBING PLAN:
4. The Uniform Plumbing Code and the International Plumbing Code are not interchangeable. Only one code may be specified for a plumbing design. Notes provided indicate plumbing to comply with the UPC and the fixture unit schedule has IPC values. Clarify.

MECHANICAL PLAN:
5. Gas appliances shall comply with combustion air requirements of Chapter 17, 2006 IRC. Confined spaces require a minimum of two 100 SQ. IN. openings, M1702.2.

ELECTRICAL PLAN:
6. As of 6/12/2007 the City of Tucson has adopted the 2006 IRC. All notes should reference this code.
7. Clarify the service panel capacity (400 amp or 200 amp).

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/09/2009 THAUSER1 OUT TO CUSTOMER Completed
12/09/2009 SUE REEVES REJECT SHELF Completed