Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T09CM02449
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2010 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS T10CM02449 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. Effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation are required for all new SFR and duplex plans. Show the code references on the plans. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes; Building Codes GENERAL NOTES: " The Inclusive Home Design is only needed for new SRF and duplexes, not additions. FLOOR PLANS: 1. Projections shall not extend to a point closer than 2 feet from the property line, and when extending into the 3-foot fire separation distance shall have not less than one-hour fire-resistive construction on the underside. Provide notation for compliance with R302.1 (City of Tucson Amended) for protecting the underside of the Garage/Storage overhang. 2. Show the garage floor direction of slope, R309.3. STRUCTURAL PLANS: 1. Provide the span of the glu-lam beam shown at section A-A for verifying the load carrying capacity, R301.1. 2. Show a beam size with appropriate load carrying capacity over the Laundry entrance and pantry, R301.1. PLUMBING PLANS: 1. Provide protection of (indoor rated) equipment located outdoors, or exterior rated enclosure, UPC 508.27. 2. Provide water hammer arresters wherever quick-closing valves are installed in a water distribution system. The devices should conform to ASSE 1010-2004. Water hammer arresters are required for the clothes washer, UPC 609.10. MECHANICAL PLANS: 1. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1. Show R-4.2 insulation when ducts are located in an unconditioned space (chase) inside the thermal envelope, IECC 503.2.7 (City of Tucson Amended). ELECTRICAL PLANS: 1. Revise the electrical riser diagram showing the Storage sub-panel, E3303. Notate the grounding and bonding method, E3507. 2. Show all receptacle outlets in the Storage accessory building with ground fault circuit interrupting protection, E3802.2. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Both standard and high density R-30 batt insulation requires a space greater than provided with 2" x 6" framing on Section B-B. Identify the product that provides the intended value, or provide a ceiling cavity space for R-30 batt insulation. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/04/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 03/04/2010 | SUE REEVES | REJECT SHELF | Completed |