Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02423
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/15/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. The manufacturer of the evaporators requires that the evaporator condensate pan be trapped. Clarify how and where the evaporator condensate drains will be trapped. Reference: Section 304.1, IMC 2006. 2. Comment not resolved. Provide the operating capacity of each of the refrigerant systems, i.e. show the capacity on the drawings. Reference: Sections 106.3.1 and 1101.1, IMC 2006. 3. Note: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). |
10/21/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/26/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
10/26/2009 | SUE REEVES | REJECT SHELF | Completed |