Permit Number: T09CM02423
Parcel: 116193770

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02423
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
09/14/2009 DAVE MANN FIRE REVIEW Approved
09/17/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/17/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/18/2009 ERIC NEWCOMB ZONING HC REVIEW Passed
09/22/2009 RMYERS1 WWM REVIEW Passed 1. no new plumbing fixtures being added.
09/22/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Passed
09/22/2009 RMYERS1 WATER REVIEW Passed
09/25/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify keynote 8 on sheet M1.1; it is shown in details 2/M1.1 and 3/M1.1 but called out as "NOT USED" in the specific notes on M1.1. Reference: Section 106.3.1, IMC 2006.
2. Clarify how and where the evaporator condensate drains will be trapped and how the condensate lines will be protected from freezing. Reference: Section 304.1, IMC 2006.
3. Provide the operating capacity of each of the refrigerant systems, including the type and amount of the refrigerant used in each independent refrigerant circuit. Reference: Sections 106.3.1 and 1101.1, IMC 2006.
4. Provide information to show that a machinery room complying with the requirements of Section 1105, IMC 2006, is not required for the refrigeration equipment located inside the building. Reference: Section 1104.2, IMC 2006.
09/30/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 255 N Commerce Park
T09CM02423
new cold storage vault

The electrical plans have been denied for the following:

1. Provide a total load calculation in order to review change on whole load. Include individual new load.
2. Provide fault current let thur from line side of manual transfer switch on through to Panel WPLD.
3.NEC 2005, 250-30 A-3 ,grounding for a seperately derived system (trans) to be obtained from tablr 250-66, which for a 2/0 cu conductor would be a # 4 not # 6.
4. Disconnects required on evaporators (fans) from ACC unit.
Ray T Majuta
Elect Plan Ck, PDS City of Tucson
10/01/09
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
10/07/2009 SUE REEVES REJECT SHELF Completed