Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG-MODEL PLAN/ENGINE/WALK THRU
Permit Number - T09CM02417
Review Name: RESIDENTIAL BLDG-MODEL PLAN/ENGINE/WALK THRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/08/2009 | JASON GREEN | ENGINEERING | REVIEW | Denied | Per Elizabeth Leibold additional information is required prior to approval. 1. Site plan must provide pad elevation along with finished floor elevations. 2. Site plan must provide statement as to weither this lot is a Lot A or Lot B drainage per TP (Lot B- rear drainage) and provide flow arrow to ensure correct grading of the lot. 3. Site plan needs to confirm the call out of elevation B as shown. If this elevation is in reference to the elevation sheets on the building set then it must be clarified (elevation B on elevation sheets has been crossed out and is no longer in use) 4. Proposed lots along north boundary, any new proposed east lots, and for future development of the lot next to west catch basin, need drainage data confirmation due to as-built conditions for the drainage structures. Therefore, Lot 14 needs to provide proposed FFE on plot plan and either: provide the revised drainage report for the subdivision that addresses current as-built drainage conditions, or provide Engineer sealed documentation for confirmation for min FFE or min FPE for the lot with respect to drainage for current conditions. Posted: JG |
| 09/08/2009 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 09/08/2009 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Approved |