Permit Number: T09CM02402
Parcel: 105097340

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T09CM02402
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2009 MARTIN BROWN FIRE REVIEW Approved
11/10/2009 Michael Wyneken PLANNING-CITY HALL REVIEW Approved
11/12/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/16/2009 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Approved
11/17/2009 STEVE SHIELDS ZONING REVIEW Approved
11/18/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Project: 50 E. Croydon Park
T09CM02402

Project denied for the following:

1. Provide one line diagram of electric service include:
- rating of service
- wire size and type
- grounding electrode system
- available fault current from utility
- available fault current at equipment and AIC rating of equipment.

Rich Jiroudek
Electric Plans Examining
520-954-0161

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2009 DELMA ROBEY OUT TO CUSTOMER Completed