Permit Number: T09CM02401
Parcel: 105095520

Address:
4888 N STONE AV

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T09CM02401
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2009 MARTIN BROWN FIRE REVIEW Approved
11/10/2009 Michael Wyneken PLANNING-CITY HALL REVIEW Approved
11/12/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/16/2009 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Approved
11/17/2009 STEVE SHIELDS ZONING REVIEW Approved
11/18/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Project: 4888 N. Stone Ave
T09CM02401

Project denied for the following:

1. Provide on line diagram showing the following:
- electric service rating
- wire sizes and type
- grouding electrode system
- Available fault current from utility transformer
- available fault current at equipment and AIC rating of equipment.

Rich Jiroudek
Electric Plans Examining
520-954-0161