Permit Number: T09CM02397
Parcel: 125080020

Address:
2222 E 8TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02397
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM02397
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

STRUCTURAL PLANS:
1. Provide complete roof framing information for determining load carrying capacity for the porch array. Show size, span and tributary for the beam, R301.1.
CALCULATIONS
1. Show a DC grounding electrode conductor size equal to the neutral conductor and not smaller than #8 (copper), NEC 250.166. Revise the wire schedule appearing on the 1 line diagram and the 3 line diagram.
NOTES / SPECIFICATIONS
1. Provide the exact wording and locations for any plaques which may be required for non co-located disconnects by NEC 690.56 (B).
2. Specify and show a continuous Grounding Electrode Conductor.
(Reference NEC 250.64 (C), 250.160.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2009 DELMA ROBEY OUT TO CUSTOMER Completed
09/10/2009 SUE REEVES REJECT SHELF Completed