Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM02388
Parcel: 13303301A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T09CM02388
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/24/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/24/2009 CAGUILA1 ZONING REVIEW Needs Review
12/24/2009 CAGUILA1 ENGINEERING REVIEW Needs Review
12/24/2009 CAGUILA1 WWM REVIEW Needs Review
12/31/2009 ROBERT SHERRY WATER REVIEW Denied Comment not addressed. Tucson Water limits a 1-1/2" meter to a maximum demand of 50 GPM. Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project (demand is 53 GPM). Reference: Sections 610.2 and 610.12, UPC 2006.