Permit Number: T09CM02359
Parcel: 13821022A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02359
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT: CONCERNING THE CANOPY FRAMING INDICATED ON SHEETS A6.1 AND A6.2, PROVIDE THE 5" S-BEAM SPACING/LOCATIONS. PROVIDE STRUCTURAL CALCULATIONS FOR ALL FRAMING AND FOUNDATIONS AT THE CANOPIES.
2. GENERAL: PROVIDE TWO COMPLETE SETS OF REVISED STRUCTURAL CALCULATIONS.
3. SHEET A1.1: THREE-3000 GALLON RAINWATER HARVESTING TANKS HAVE BEEN ADDED TO THIS PROJECT. AN ADDITIONAL ZONING REVIEW IS REQUIRED. ON THE PLANS, PROVIDE PHYSICAL TANK SIZES, OVERFLOW PROVISIONS, AND DETAILS OF THE TANK FOUNDATION AND HOW THE TANK IS CONNECTED TO THAT FOUNDATION.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/19/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
05/26/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2010 CPIERCE1 OUT TO CUSTOMER Completed
08/26/2010 CPIERCE1 REJECT SHELF Completed