Permit Number: T09CM02338
Parcel: 14002010A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02338
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2009 MARTIN BROWN FIRE REVIEW Approved
09/29/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
09/29/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.0; STRUCTURAL NOTES: NOTE 7 INDICATES A SOIL REPORT WAS USED IN DETERMINING THE ALLOWABLE BEARING PRESSURE. PROVIDE THAT REPORT FOR REVIEW.
2. SHEET S2.0; GENERAL FOUNDATION NOTES: NOTE 5 INDICATES MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS, WHICH ARE NOT RELEVANT TO THIS PROJECT. REMOVE NOTE.
3. SHEET S3.0; FRAMING PLAN: THE STRUCTURAL CALCULATIONS INDICATE BEAM DB6 REQUIRES A W18X35 (SHEET 7) OR W14X26 (SHEET 18), AND THE DRAWING INDICATES A W14X26. CLARIFY.
4. GENERAL: PROVIDE COLUMN BASE PLATE AND ANCHOR BOLT DESIGN CALCULATIONS.
5. GENERAL: PROVIDE AN EXPLANATION OF THE LATERAL LOAD RESISTANCE FOR THE EARTHQUAKE FORCE (10,557 POUNDS) APPLIED TO THE STRUCTURE AS INDICATED IN THE CALCULATIONS (PAGE 20). DID NOT SEE WHERE ANY APPLIED MOMENT (20,187 FT/LBS) TO THE NEW COLUMN (M4) ON PAGES 23-42 WAS USED IN THE COLUMN DESIGN (DC1 ON PAGES 43-45). IS THIS LATERAL LOAD TO BE APPLIED AT BOTH GRIDS B.1 AND B.8? CLARIFY FOR THE REVIEWER.
6. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
10/01/2009 SUE REEVES REJECT SHELF Completed