Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02329
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/01/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
09/01/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
09/02/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
09/02/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE STRUCTURAL, FULL SIZE DRAWINGS WITH STRUCTURAL DETAILS AS INDICATED IN THE CALCULATIONS, OR INCLUDE STRUCTURAL DETAILS ON AN ARCHITECTURAL SHEET OF THE DRAWINGS. |
09/02/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Passed | |
09/02/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how ventilation air is being provided to the server room. Reference: section 403.3, IMC 2006. 2. Note that materials exposed in plenums shall conform to Section 602.2.1, IMC 2006. 3. Provide information to show that a machinery room is not required for the refrigeration equipment located inside the server room. Reference: Section 1104.2, IMC 2006. |
09/03/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project; 7840 E Broadwat Bl, T09CM02329 TI Office The Electrical Plans have been denied for the following: 1. Provide a Fault Current calculation for the Electrical Service beginning at the Service on through to the Panels. 2. Provide the size of conductors and conduit from the new 1200 Amp service to the existing CT can. 3. Provide the location of the EPO switch on the power plan. Ray T Majuta Elect Pln Ck PSDS City of Tucson 9/7/09 Ray.Majuta@tucsonaz.gov |
09/03/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/03/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
09/03/2009 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
09/03/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show that location of the reduced pressure backflow preventers conforms to the access and clearance requirements of Section 603.3.4, UPC 2006. |