Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02329
Parcel: 13414001K

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02329
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
09/01/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
09/02/2009 ERIC NEWCOMB ADA REVIEW Passed
09/02/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE STRUCTURAL, FULL SIZE DRAWINGS WITH STRUCTURAL DETAILS AS INDICATED IN THE CALCULATIONS, OR INCLUDE STRUCTURAL DETAILS ON AN ARCHITECTURAL SHEET OF THE DRAWINGS.
09/02/2009 ERIC NEWCOMB ZONING HC REVIEW Passed
09/02/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/03/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how ventilation air is being provided to the server room. Reference: section 403.3, IMC 2006.
2. Note that materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
3. Provide information to show that a machinery room is not required for the refrigeration equipment located inside the server room. Reference: Section 1104.2, IMC 2006.
09/03/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project; 7840 E Broadwat Bl, T09CM02329
TI Office

The Electrical Plans have been denied for the following:

1. Provide a Fault Current calculation for the Electrical Service beginning at the Service on through to the Panels.
2. Provide the size of conductors and conduit from the new 1200 Amp service to the existing CT can.
3. Provide the location of the EPO switch on the power plan.



Ray T Majuta
Elect Pln Ck
PSDS City of Tucson
9/7/09
Ray.Majuta@tucsonaz.gov
09/03/2009 ROBERT SHERRY WATER REVIEW Approved
09/03/2009 MARTIN BROWN FIRE REVIEW Approved
09/03/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
09/03/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show that location of the reduced pressure backflow preventers conforms to the access and clearance requirements of Section 603.3.4, UPC 2006.