Permit Number: T09CM02318
Parcel: 99999999A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02318
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved. Section 1101.11.2.1, UPC 2006 calls for the scupper to have a minimum width equal to the circumference of the required roof drain as determined with Table 11-1, UPC 2006. The minimum scupper height shall be 4". (The policy for the City of Tucson will allow the scupper to also serve as an overflow if the scupper height is increased to 6".) If you wish to use a circular scupper, submit an appeal to the building offical and provide the calculations that show it will have performance at least equivalent to the code-minimum scupper.
2. The "concealed internal temperature control mixer" will not guarantee a maximum temperature of 110 degrees Fahrenheit. Provide an ASSE listed device to control the water temperature.
10/16/2009 THAUSER1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/16/2009 THAUSER1 OUT TO CUSTOMER Completed