Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM02318
Parcel: 99999999A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02318
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
09/21/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/21/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vent to protect the floor drain trap.
2. The expansion tank shall have no check valves between it and the water heater.
3. Section 1101.11.2.1, UPC 2006 calls for the scupper to have a minimum width equal to the circumference of the required roof drain as determined with Table 11-1, UPC 2006. The minimum scupper height shall be 4". (The policy for the City of Tucson will allow the scupper to also serve as an overflow if the scupper height is increased to 6".) If you wish to use a circular scupper, submit an appeal to the building offical and provide the calculations that show it will have performance at least equivalent to the code-minimum scupper.
4. Clarify the "concealed internal temperature control mixer", i.e provide the ASSE listing for the device.
09/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/21/2009 ROBERT SHERRY WATER REVIEW Approved
10/07/2009 CAGUILA1 WWM REVIEW Needs Review