Permit Number: T09CM02318
Parcel: 99999999A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM02318
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
08/31/2009 STEVE SHIELDS ZONING REVIEW Approved
08/31/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/31/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, NSF, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006.
2. Provide a floor drain in the restroom. Reference: Section 305.0, UPC 2006.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
4. Provide an expansion tank or other approved device for controlling thermal expansion for storage-type water heaters. Reference: Section 608.3, UPC 2006.
5. Provide calculations to show that the proposed scupper can accommodate the design rainfall without exceeding a 2" depth of flow as well as provide overflow capacity or provide structural calculations to show that the roof is capable of supporting the additional rain load. Reference: Sections 1101.11.1 and 1101.11.2.1, UPC 2006, and Section 1611.1, IBC 2006.
08/31/2009 ERIC NEWCOMB ADA REVIEW Passed
08/31/2009 PAUL MACHADO ENGINEERING REVIEW Approved
08/31/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide the capacity of the proposed ventilation fan and indicate how it will be ducted out of the building.
08/31/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE CALCULATIONS FOR VERTICAL AND LATERAL ANALYSIS FOR BUILDING, INCLUDING FRAMING AND FOUNDATIONS.
08/31/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/31/2009 DAVE MANN FIRE REVIEW Approved
09/21/2009 CAGUILA1 WWM REVIEW Needs Review
09/21/2009 CAGUILA1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2009 CINDY AGUILAR OUT TO CUSTOMER Completed