Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02311
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/28/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/28/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed; please read the referenced code section. The specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006. 2. Comment not addressed. The drawings do not indicate the slope of the gutter or the size of the downspout. Also, it is not clear if the main roof has any gutters; if not, then include the contributing area of the main roof when determining the size of the gutters and downspouts for the two restrooms. See Table 11-3, UPC 2006 for the gutter size and Table 11-1, UPC 2006 for the downspout size. Reference: Section 1101.11.1, UPC 2006. |
| 04/28/2010 | CRAIG GROSS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/03/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 05/03/2010 | SUE REEVES | REJECT SHELF | Completed |