Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02311
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/03/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | Will need F.D. key boxes or locks on access gates noted on plans |
| 11/06/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/09/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 11/17/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | The water meter policy adopted on January 3, 2005 by Tucson Water states that there shall be no more than one public water meter per business. Clarify the status of the existing 1" yard water line that is shown upstream of the new 1" water meter. Is it a public or private water line? If both meters are to be used, provide a letter from Tucson Water allowing the use of two water meters for this building. Reference: Sections 103.2.3, UPC 2006. |
| 11/17/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. With regard to the wall-mounted condensing units (HP-1 and HP-2), place your mounting instructions on the drawing. Structural calculations will not be required. Reference: Sections 106.3.1 and 302.1, IMC 2006. 2. Comment not resolved; providing an integral condensate pump (note #3, Ductless Heat Pump Unit Schedule, M1.0 and keynote #6, sheet P1.0) is not the same as deleting the pump. If the condensate from the indoor units is being pumped, it shall not terminate into the tailpiece of a lavatory. Reference: Section 805.0, UPC 2006 |
| 11/17/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006. 2. The roof drainage calculations do not indicate the slope of the gutter or the size of the downspout. See Table 11-3, UPC 2006 for the gutter size and Table 11-1, UPC 2006 for the downspout size. Reference: Section 1101.11.1, UPC 2006. 3. Provide CW shut off valves for each building water entrance. Reference: Section 605.2, UPC 2006. |
| 11/19/2009 | TERRY STEVENS | ZONING | REVIEW | Denied | 11/23/2009 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/08/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 12/08/2009 | SUE REEVES | REJECT SHELF | Completed |