Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02311
Parcel: 116120430

Address:
801 N GRANDE AV

Review Status: Completed

Review Details: SITE

Permit Number - T09CM02311
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2009 DAVE MANN FIRE REVIEW Denied The framing in the exterior walls shall be steel, masonry or fire treated wood per IBC 602.3.
09/02/2009 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T09CM02311
801 N. Grande
Site Plan

TRANSMITTAL DATE: 9/02/09

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Provide a copy of the last approved site plan for review comparison. Additional comments may be forth coming based on this plan.

2. This site contains four (4) separate parcels therefore you will need to show how the parcels can work as stand alone parcels if sold separately or provide verification that a Pima County Tax Parcel Combination has been completed.

3. DS 2-02.2.1.5 Provide all lot line distance and bearings.

4. DS 2-02.2.1.8 Provide in the parking calculations the square footage of the assembly area and the required ratio (1:50) in order to verify the number of required parking spaces.

Please provide a detail of both a standards parking space and a handicap parking space. Refer to development standard 3-05.0 for design criteria for standard parking and the IBC for handicap parking criteria.

5. DS 2-02.2.1.9 Please provide a plan view detail of the proposed class 2 bicycle parking spaces. Single rack spaces placed in a row will allow a minimum of seventy -two (72) inch length per bicycle parking space and a minimum of thirty (30) inches between outer spaces of racks. A five (5) foot wide access aisle measured from the front or rear of the seventy-two (72) inch long parking space will be provided beside each row. Lighting will be provided such that all facilities are thoroughly illuminated and visible from adjacent sidewalks, parking lots, or buildings, during working hours.

Provide a detail of the proposed class 2 bicycle rack. See DS 2-09 for approved type of racks.

6. DS 2-02.2.1.11 Clearly indicate the 3' clear area required behind all backup spurs shown on the site plan. See DS 3-05.2.2.D and Figure 2.
If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T09CM02311.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
09/03/2009 RONALD BROWN ZONING HC REVIEW Denied 1. Please provide large scale detail of accessible parking showing compliance with 2006 IBC, Section 1106 and ICC (ANSI) Section 502. Show all critical accessible dimensions, slopes, ramps, signage and connection to accessible route.
2. One of every six accessible spaces must be "Van Accessiblee". Please identify such.
3. Please provide accessible parking signage detail includiong a "Van Accessible" sign.
END OF REVIEW
09/09/2009 ANDREW CONNOR LANDSCAPE REVIEW Needs Review 1. Submit a copy of the last approved site and landscape plans for reference. The application will be reviewed for compliance when the approved documents are included in the submittal. Revise site plans as necessary to comply with Zoning comments and concerns.

2. Additional comments may apply
09/09/2009 ANDREW CONNOR NPPO REVIEW Approved
09/10/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. the location and size of the public sanitary sewer and
d. the location, invert, and rim elevation of all manholes and cleanouts.
Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006.
2. Show the finished floor elevations for the buildings. Reference: Sections 103.2.3 and 710.0, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
10/13/2009 SUE REEVES REJECT SHELF Completed