Permit Number: T09CM02299
Parcel: 12701005D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02299
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2009 LEERAY HANLY ZONING HC REVIEW Approved
09/16/2009 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/21/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Approved
09/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The use of ASHRAE Standard 62.1-2004 for ventilation calculations for multiple-zone systems supplied by a single air handler requires the use of the calculations covered by Section 6.2.5, ASHRAE Standard 62.1-2004 to determine the design outdoor air intake.
2. Clarify how HP-6 is being operated. The drawing shows air being supplied to a corridor that is not included in the ventilation calculations and the drawing also omits the amount of air being supplied to the three offices and file room. The unit is scheduled to supply a total of 1600 CFM but the mechanical plan shows it delivering 1800 CFM to a corridor and rooms 148A, 142, and 140, but no air to rooms 144, 145, 146, and 147.
3. Resolve the disparity between the outside air quantities scheduled for HP-2, HP-5, HP-6, HP-7, and HP-8 on sheet M3.0 and the ventilation calculations.
4. No ventilation calculations are included for HP-3, HP-4, and HP-9.
5. The ventilation calculations show an existing 5-ton unit supplying air to a room 171 but there is no room 171 in the architectural plans; could it actually be supplying air to room 170? If so, it is also supplying air to room 162 along with another existing unit and HP-9.
6. Provide duct smoke detectors for units HP-3, HP-4, HP-5, and HP-7. Reference: Section 606.2.1, IMC 2006.