Permit Number: T09CM02299
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02299
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2009 DAVE MANN FIRE REVIEW Approved
08/31/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project; 5151 E Broadway Bl #105
T09CM02299
TI Post Secondary ED

The Electrical Plans have been denied for the following;

1. Sheet E-5 is showing several circuits marked EGP-14,16,18,20,22, which do not appear on the Panel Schedule.
2. Sheet E-11 shows two Panels marked EGP.



Ray T Majuta
Elect Plan Ck
PDS City of Tucson
9/1/09
Ray.Majuta@tucsonaz.gov
09/02/2009 GERRY KOZIOL WWM REVIEW Approved
09/03/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: A MINIMUM OF 3/32" HIGH LETTERING IS REQUIRED ON ALL DRAWINGS (SHEETS A-1.0, A-1.1, A-1.2, AND A-1.3). REVISE.
2. GENERAL: PROVIDE AN ANALYSIS ON THE DRAWINGS INDICATING THAT THE PLUMBING SYSTEMS REQUIREMENTS (COMBINED NEW AND EXISTING) PER THE IBC ARE ADEQUATE FOR THE NEW OCCUPANT LOADING IN THE EAST AND WEST WINGS.
09/04/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
09/04/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the West Wing Plumbing Schedule with the floor plans for the number of fixtures shown on the floor plans. Reference: Sections 103.2.3 and 610.1, UPC 2006.
2. Clarify why the waste water fixture units for the existing fixtures have been omitted from the plumbing schedules. Reference: Section 13.2.3, UPC 2006.
3. Clarify why the water and waste water fixture units from the plumbing demo schedule for the west wing have been subtracted from the fixture units for the new and the retained existing fixtures. Reference: Section 13.2.3, UPC 2006.
09/04/2009 ROBERT SHERRY WATER REVIEW Approved
09/04/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006.
2. Provide a description of the occupancy category used for each room in the ventilation calculations to justify the occupant densities and combined outdoor air rates used in the ventilation calculations. Reference: Sections 106.3.1 and 403.2, IMC 2006, as amended by the City of Tucson; ASHRAE Standard 62.1-2004.
3. Note that materials exposed in plenums shall conform to Section 602.2.1, IMC 2006

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2009 DELMA ROBEY OUT TO CUSTOMER Completed