Permit Number: T09CM02267
Parcel: 133110010

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T09CM02267
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2009 STEVE SHIELDS ZONING REVIEW Approved
10/28/2009 RONALD BROWN ADA REVIEW Denied PREVIOUS COMMENTS NUMBERS 1 AND 2:
1. Please submit a letter summary of deferred submittals to Mr. LeeRay Hanley for approval.
PREVIOUS COMMENT NUMBER 3:
4. Please reference sheet numbers G5, C1, C2, C4, C5, I1, E1, E4 and SWP3.
PREVIOUS COMMENTS NUMBER 4:
5. As per ADAAG, Section 4.1.3. (19) (a), the companion fixed seat shall be identified by a sign or marker as outlined by Section 4.30 Signage.
6. It is also recommended that the each designated wheelchair area be marked with a perimeter outline stripe and the international accessible symbol as per Section 4.30.
PREVIOUS COMMENTS NUMBERS 5 AND 6:
7. OK
PREVIOUS COMMENTS NUMBER 7
8. Please revise the location of the accessible parking signage noted on detail 5/C-6 to be just outside the 18' depth of the parking space into the concrete curb/sidewalk area.

END OF REVIEW
10/30/2009 ANDREW CONNOR LANDSCAPE REVIEW Approved
11/03/2009 JASON GREEN ENGINEERING REVIEW Approved
11/03/2009 ANDREW CONNOR NPPO REVIEW Approved
11/12/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/17/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT: MORRIS UDALL PARK
7290 E TANQUE VERDE RD
T09CM02267
FIELD LIGHTING

The electrical plans have been denied for the following:

1. Provide cut sheets on fixtures being used,those being installed by Mussco need not be provided if they are obtaining their own permit.
2. Indicate on Sheet E-1 circuits to be assigned to lighting.
3. On sheet E-1, there are 10 P1 fixtures shown, also there are 6 W1 fixtures shown. In the lumen calculations on Sheet E-4 there are 8 P1 fixtures and 9 W1 fixtures ?
4. Cannot locate 2 F1 fixtures and 4 F2 fixtures shown on Sheet E-4, nor are they on the fixture schedule.
5. How is the 125% for continuous duty on lighting figured on the load calculations on Sheet E-2.
6. Is Panel C for the Concession Stand to be re-fed(existing), or new but to be installed by others?

Ray T Majuta
Elect Pln Ck, DPDS City of Tucson
11/08/09
Ray.Majuta @tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2009 CPIERCE1 OUT TO CUSTOMER Completed
12/01/2009 SUE REEVES REJECT SHELF Completed