Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02266
Parcel: 132250650

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T09CM02266
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2009 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. A 30" continuous screen along street frontages for vehicle use area must be provided per LUC Table 3.7.2-I. Identify all screening elements on the landscape plan

2. A 6' screen is required for storage areas along street(s) per LUC Table 3.7.2-I. Additional plants are needed to satisfy screening requirements.

3. Screen planting can be aligned, clustered, or unevenly spaced to provide interest as long as the plants provide a continuous screen, at maturity.

4. The screening requirement is in addition to the landscape requirements. The use of vegetation to satisfy the screen requirement is allowed only to provide for alternative treatment and is not in any way meant to imply that the vegetative screen can also be used to meet the landscape requirement. Revise coverage calculation if necessary.

5. Ensure that any changes to the site plan are reflected on the landscape plan.

6. Additional comments may apply
10/21/2009 ANDREW CONNOR NPPO REVIEW Approved
10/21/2009 MARTIN BROWN FIRE REVIEW Approved
10/30/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: October 30, 2009
SUBJECT: Site Plan
TO: A23 Studios (Jose)
LOCATION: 4261 E Irvington, T14S, R14E, Section 34, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T09CM02266 (Second Review)


RESUBMITTAL REQUIRED: Site Plan, Drainage Report

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the Site Plan.

Site Plan:

1. Complied.
2. DS Sec.2-02.2.1.A.4: Revise the project location map on Sheet 1 of 3. The map should include labeled section corners.
3. Label both existing and future sight visibility triangles per D.S. 2-02.2.1.10. If existing and future sight visibility triangles are the same, label both existing and future right of way.
4. Complied
5. DS Sec.2-02.2.1.A.11 & DS Sec.3-01.3.2.C: Depict and label radii concrete curbs per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213) at the driveway entrance along Irvington Rd.
6. Indicate curb returns for MS&R and call out radius on plans.
7. Must comply with all zoning comments regarding pedestrian access.
8. DS Sec.2-02.2.1.A.12: Revise the site plan to show the required 6-foot wide sidewalk with curb along the street frontage of Irvington Road. Per the adopted Mayor and Counsel policy all sidewalks along MS&R right-of-ways for arterial and collector streets require 6-foot wide sidewalks.
9. Complied
10. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14. DS Sec.2-02.2.1.A.14: Provide (label and dimension) the required onsite maneuvering area for the loading zone that is shown adjacent to the proposed building. Refer to AASHTO for the national standards for turning radii. Call out all turning radaii on plan.
11. Please provide Drainage patterns and finished grades and percentage slopes per D.S. 2-02.2.1.16.
12. DS Sec.2.02.2.1.A.16: Provide drainage arrows and locations of all concentration points. Specifically show roof down spout locations for buildings at pedestrian circulation areas. If scupper is provided, a detail for the dimension of the proposed scuppers used will be needed for collecting onsite roof drainage at all pedestrian sidewalks, refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Drainage statement should show scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk.
13. Grading permit will be required.
14. Indicate and label existing and future right-of-way if existing and future right of way label existing/future.
15. Complied
16. Complied
17. DS Sec. 2-05.2.4.H.2: Provide the right-of-way (ROW) recordation information for Irvington Rd. Please identify recordation number on site plan.
18. Complied
19. Complied
20. Add contour to the east of parcel to better demonstrate drainage scheme or add spot elevations. Provide contour interval on plan below scale and north arrow: Contour Interval = 1'.
21. Complied
22. Complied
23. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. See enclosed detail and provide your own detail in plan set for next review. Revise plans so that dimensions are viewable. See attached detail for reference.
24. Complied
25. Show 14' X 40' clear approach and show access dimensioning to proposed trash enclosure. In addition, provide maneuverability on site along with radaii and dimensions.
26. Standard Note: Be advised a permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
27. Show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the driveway, if applicable.
28. Complied
29. All symbols on plans need to be indicated in legend. Indicate all symbols in legend.
For any development with 50 cy of cut or fill will require grading plan and for any site with area of disturbance of one acre or greater a Stormwater Pollution Prevention Plan will be required. It looks from aerial that grading has taken place on site already. "A grading permit and Stormwater Pollution Prevention Plans (SWPPP's) will likely be required for this project. In the event that they are needed, Submit 3 sets of grading and (2) SWPPP's with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".
30. Per site visit on 10/15/09 grading appears to be all the way to the property line. Address the following:
a) There is a minimum 2' setback from property line to tow of fill.
b) Provide note on site plan indicating that minimum 2' setback will be met.
c) Call out slope between 2' setback and top of fill.
d) Show positive drainage to retention/detention basin.
31. Provide cross section for basin and show spot elevations of basin bottom, sides and top of basin. In addition, provide second cross section for area rip rap area identified by keynotes 14 and 15.
32. Specifically show spot elevations at the property line of driveway to show drainage is being kept on site.
33. Addition comments may be forthcoming.

Drainage Report:

1. Off site drainage along Irvington does not appear to be addressed. Provide additional information in hydrology section addressing the off site flood conditions in Irvington.
2. Include floodplain limits on plan for any 100 year flows that are on site and show how the proposed design considers any impact from jurisdictional floodplain.
3. Include all weather access design if floodplain limits encroach onto property.
4. Show existing and proposed flows entering and exist the site at all boundaries of the lot.
5. Not that grading design will need to be in compliance with revised hydrology. Please address hydrology prior to submitting grading plan to prevent duplication of comments.
6. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
11/03/2009 DAVID RIVERA ZONING REVIEW Denied DSD TRANSMITTAL

FROM: David Rivera
Principal Planner

PROJECT: T09CM02266
4261 E Irvington Road
Site Plan (Construction Service Use?)

TRANSMITTAL DATE: November 3, 2009

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

This plan was reviewed for compliance with the Site Plan Content and Specifications 2-02 and applicable development standards which include but is not limited to sections 2-05, 2-08, 2-09, 3-01, 3-05, and applicable LUC development criteria.

It was requested that the previous plans or redlines be resubmitted with the revised set of drawings. This was not done please ensure that the redline copy of the plans are resubmitted with the next submittal of the site plan.

1. This was not addressed. The sections corners info was requested for the location map.

Previous Comment 1: Label applicable sections corners as redlined on sheet A1.0. DS 2-02.2.1.A.4 and DS 2-05.2.1.D.3

2. The use has been clarified per your response and some of the notes. The issue still remaining is the storage areas proposed. The numbers do not add up.
a. Clearly define the storage areas and label them appropriately with distance and square footages.

b. I can verify on the plan by keynotes 19 the two areas that are considered outdoor storage which total 22, 279 square feet.

c. Keynote 7 indicates that two 8'x40' Storage containers will be placed on the existing concrete slab just north of the proposed building. The slab area is annotated as 2,393 square feet of storage area. Which is correct? Is the entire slab area going to be used for storage in which case the total square footage would be greater than the two proposed containers? Revise the notes and make it clear what is proposed for this area.

d. Keynote 8 indicates an existing concrete pad, is this pad to be used for storage as well or what is the use for the concrete pad? Dimension and add list the square footage of the pad.

e. The areas around the storage areas have been annotated with keynote 9. What is the proposed use for this area? It is not clear what is the intended use is for this area with gravel, 2" screened rock, asphalt millings.

Previous Comment 4: As of this review it is not clear what the specific principal use for this site is going to be. The proposed use listed on sheet A1.0, Site Info note 3 indicates Field Office and Storage Yard. The parking requirement cannot be verified at this time and will be reviewed on the next submittal once a principal use is listed. Revise the parking calculation based on the actual principal use. If multiple uses are proposed for this site list all uses and include the relevant development data associated with each use. DS 2-02.2.1.A.8


3. Once the overall storage areas have been determined, which in turn will determine the number of required/provided vehicle parking spaces can the number of bicycle parking based required be determined. (I don't believe that more than bicycle parking spaces will be required unless a substantial amount of vehicle parking is added.)

The information related to the information and detail drawing(s) was not provided on the plan as requested per my last comment.

Previous Comment 5: The number of required bicycle parking spaces cannot be verified at this time until the principal use is listed correctly. Ensure that Off-street bicycle parking, including materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports; and the location and type of directional signage. Include a bicycle parking calculation based on the requirement for class on and two facilities or as required based on the use. DS 2-02.2.1.A.9

4. The future sight visibility triangles have not been depicted on the plan. The future roadway curb has not been depicted on the plan. Verify with transportation where the future curb is proposed and drawn and label the future SVT's as required.

Previous Comment 6: Existing and future sight visibility triangles must be drawn and labeled on the site plan sheet. Draw and label the existing and future sight visibility triangles correctly and based on existing and future curb locations. See DS 3-01 for correct placement of SVT's. Consult with the DSD engineering reviewer for the locations and requirements. DS 2-02.2.1.A.10

5. The location of the sidewalk from the property line is not acceptable as shown. The portion of the sidewalk in front of the dumpster must be located around the back of the enclosure area or relocate the sidewalk entirely. (It is suggested that the sidewalk be relocated and aligned with the Access Aisle next to the Disabled parking space.)

Also, the portion of the sidewalk that is parallel with the parking spaces (with the exception of the disabled access aisle) closest to the street property line is not physically separated and may not be asphalt or chip seal. The sidewalk must be constructed of concrete and raised above the pavement or may be flush with the pavement and constructed of concrete and can be physically separated with extruded curbing or bollards.

A portion of previous comment 8: A continuous pedestrian circulation is required from the street sidewalk or the from the property line (if there is currently no sidewalk or requirement for a street sidewalk) to all structures on the site. The minimum width for any required sidewalk is four (4) feet. The sidewalk must be physically separated from the all vehicular use areas. Separation may be provided by a raised concrete sidewalk, vertical curbing, permanent bollards with chain or cable a minimum of 6 feet a part etc. All sidewalks must be constructed of concrete a minimum of four (4) inches thick. The required path must also meet ADA or ANSI accessibility requirements, see Ron Brown's comments with regards to accessibility. Chip seal or pavement is not acceptable for the pedestrian circulation.

In addition, all public access areas on the site must be connected as noted in DS 2-08.3.1. This section excludes required concrete sidewalks if there is no public access beyond the main office building. In cases where the public is not allowed access to certain areas such as the canopy, slab etc a striped employee path of pavement is allowed. The path must be a minimum of four feet wide.
DS 2-02.1.A.12

6. This comment was not addressed as with the requested details and information.

Previous Comment 9: Draw and label the bicycle parking facilities and add the required dimensioned detail drawings for class one and two facilities. DS 2-02.2.1.A 12

7. The previous comment was not addressed in full as requested. Specifically the first sentence.

Previous Comment 12: Draw, label and dimension the future curb and sidewalk on Irvington Road based on the future roadway requirements. All easements of record must be graphically shown on the plan together with recording docket and page reference.
DS 2-02.2.1.A.19 and DS 2-02.2.1.A.21

8. Has Andy Vera confirmed the location of the dumpster enclosure? If so this comment can be disregarded. Provide a copy of the confirmation.

Previous Comment 16: Contact Andy Vera of Environment Services with regards to the proposed refuse location and enclosure requirements. DS 2-02.2.1.A.32

9. Not all the items listed in this comment were added to the cover sheet. Review the list and ensure that all items are addressed and added to the plans sheets.

Previous Comment 17: The following items must be listed on the cover sheet, DS 2-02.2.2.A.1-.6
-Principal use and development designator,
-Parking ratio with the number of spaces required and spaces provided which include required - Disabled parking spaces,
-Floor Area Ratio (FAR) allowed and proposed,
-Bicycle parking spaces required and proposed (class one and two),
-Loading zones required and proposed and size based on the principal use,
-Total lot area,
-Correct Building setbacks - interior and street setback requirements, (Street setback is incorrect),
-Building heights allowed and proposed,
-Building square footages and outside use areas associated with the use,

A. The following calculations are required on the site plan, including the methodology. If there is not enough space on the site plan to include these calculations, another plan sheet is used.
1. Gross and net lot area.
2. Floor area for each building.
3. Percentage and area in square feet of building and accessory building coverage.
4. Vehicular and bicycle parking spaces required and provided, including handicapped.
5. Number of loading spaces required and provided.
6. Percentage of building or lot area expansion. If the building(s) or lot area has been previously expanded, those calculations shall be included.

10. This comment was not addressed and yes the AEZ affects this property.

Previous Comment 19: Indicate on the plan how all buildings or work areas will comply with the AEZ requirement for the NCD 65 Ldn (NCD-65).

11. Please review the previous redlines and green lines and address any remaining comments.

Previous Comment 20: Review the redlines made on the site plan copy and make any applicable changes or revisions to the plans as necessary. All green lines are zoning related.

12. Additional comments may be forthcoming based on the revisions to the plan sheets and response comments.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

C:\planning\cdrc\DSD\T09CM02266b.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
11/09/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The site drawing shows no connection from the office trailer to a public sewer and no septic system. How is the waste disposal for the office trailer accomplished? Reference City of Tucson Development Standard No. 2-05.0 3.8D.
11/12/2009 RONALD BROWN ZONING HC REVIEW Denied 1. OK

2. On the accessible parking detail, please show access from the aisle to the concrete accessible route. Show all grade differentiations, ramps as required, slopes and signage.
THIS NEEDS TO BE NOTED AND SHOWN ON THE SITE PLAN AND DETAILS.

3. The one accessible space provided must be "Van Accessible". Please identify such on plan and provide a "Van Accessible" sign on the sign detail. The new fine rate is $532.00.
PLEASE IDENTIFY THE VAN SPACE ON THE SITE PLAN AND PROVIDE A "VAN ACCESSIBLE SIGN ON THE ACCESSIBLE SIGN POST DETAIL.

4. OK

5. OK

ADITIONAL COMMENT:
6. Reference Zoning comments for your new accessible route in front of the Dumpster enclosure and finish material of that route section. If allowed to remain, a marked crossing will be necessary across the front of the dupster area.


END OF REVIEW