Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM02252
Parcel: 14042002A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02252
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2009 TERRY STEVENS ZONING REVIEW Approved
08/24/2009 LOREN MAKUS ENGINEERING REVIEW Approved
08/25/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/25/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the existing ventilation is adequate for the proposed occupancy.
08/25/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. COMBINE ADDITIONAL OFFICE SQUARE FOOTAGE WITH EXISTING SQUARE FOOTAGE TO DETERMINE TOTAL OCCUPANT LOAD. THIS WILL DETERMINE YOUR REQUIRED PLUMBING FIXTURE COUNT (SERVICE SINK, RESTROOMS, DRINKING FOUNTAINS, ETC).
2. PROVIDE VERBAGE AND/OR A DRAWING INDICATING TRAVEL DISTANCES FOR RESTROOM REQUIREMENTS.
08/25/2009 ROBERT SHERRY WATER REVIEW Approved
08/25/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied If hot water is supplied to the new lavatory, show how the water temperature is limited to a maximum of 110 degrees Fahrenheit.
08/25/2009 DAVE MANN FIRE REVIEW Approved
08/25/2009 ERIC NEWCOMB ADA REVIEW Passed
08/25/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/25/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
08/31/2009 THAUSER1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2009 THAUSER1 OUT TO CUSTOMER Completed