Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02251
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2009 | DAVE MANN | FIRE | REVIEW | Denied | Panic hardware is required for group E occupancies with an occupant load over 50. IFC 1008. The occupant load should be one per 20 sf for a class room. IFC 1004. |
| 09/08/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/08/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/08/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/14/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/18/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/24/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 09/24/2009 | SUE REEVES | REJECT SHELF | Completed |