Permit Number: T09CM02241
Parcel: 13109226A

Review Status: Active

Review Details: SITE

Permit Number - T09CM02241
Review Name: SITE
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2009 DAVE MANN FIRE REVIEW Denied No fire access to rear of buiding. Fire separation required between retail and automotive repair.
08/21/2009 ANDREW CONNOR NPPO REVIEW Passed
08/21/2009 ANDREW CONNOR LANDSCAPE REVIEW Passed
08/21/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/21/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
08/21/2009 RBROWN1 ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
08/21/2009 JASON GREEN ENGINEERING REVIEW Denied 1) Existing utility pole blocks access to proposed parking space. Conflict with entering and existing spaces. Pole must be removed and utility line must be placed underground to eliminate conflict.

2) PAAL north of building must be minimum 24-feet for 2 way traffic, 12- feet for one way and 20-feet for access to refuse container. Currently the plan shows 11-feet 1 inch which does not meet the minimum requirements.

3) Verify that the refuse container does not block access to parking spaces in the back. Verify that the refuse container is built per DS Sec 6-01 (Figure 3). Refer to Environemntal Services for clarity.
08/21/2009 RONALD BROWN ZONING HC REVIEW Approved