Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02207
Parcel: 13405118L

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM02207
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2009 DAVE MANN FIRE REVIEW Denied A type 1 hood and supression is required.

Indicate if alarm system is being modified.
09/09/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the submitted design to provide a Type I hood over the two hot plates. The design shall comply with Sections 506, 507, and 508, IMC 2006 for Type I hood systems.
2. Provide structural calculations and details to show that the Type I hood system is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
09/09/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The code review on sheet G-101 indicates that there is an existing drinking fountain. Where is it located? Reference: Section 103.2.3, UPC 2006.
2. Provide a floor drain in the kitchen. Reference: Sections 411.2.2 and 704.3, UPC 2006.
3. Provide water pressure and water pipe sizing calculations; show that the additions to the existing piping do not result in local overloading of the water distribution piping. Reference: Sections 101.5, 610.1, and 610.3, UPC 2006.
4. Verify that an expansion tank or other approved device for controlling thermal expansion for storage-type water heaters has been installed. Reference: Section 608.3, UPC 2006.
5. Provide indirect waste piping for the prep sink. Reference: Section 801.2, UPC 2006. (Note: the wash and rinse compartments of a 3-compartment sink are directly-connected, the sanitizing compartment is indirectly-connected.)
6. Clarify how the indirect waste receptor is to be installed: indirect waste receptors shall not be installed in a closet or cupboard but shall be accessible for inspection and cleaning. Reference: Section 804.1, UPC 2006.
09/09/2009 ROBERT SHERRY WATER REVIEW Denied 1. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2009 CPIERCE1 OUT TO CUSTOMER Completed
09/14/2009 SUE REEVES REJECT SHELF Completed