Permit Number: T09CM02154
Parcel: 129020470

Review Status: Active

Review Details: REVISION - - 2ND

Permit Number - T09CM02154
Review Name: REVISION - - 2ND
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise detail 2/M2.1 to comply with the requirements of Section 506.3, IMC 2006.
2. Clarify the revision to the return ductwork for existing A/C unit D: it appears that the new 26x14 SA duct is being connected to a 26x22 RA duct.
02/18/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
02/18/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the locations where keynotes 60 and 61 occur. Are the noted water heaters the same as WH-1 and WH-2? Water heaters WH-1 and WH-2 are specified as electric, not gas on sheet P3.1.
2. Provide revised gas piping notes reflecting the new total gas load; the total gas load (keynote 37) doesn't agree with the identified loads.
3. How is combustion air being provided for the water heaters?