Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Active
Review Details: REVISION - - 2ND
Permit Number - T09CM02154
Review Name: REVISION - - 2ND
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/18/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise detail 2/M2.1 to comply with the requirements of Section 506.3, IMC 2006. 2. Clarify the revision to the return ductwork for existing A/C unit D: it appears that the new 26x14 SA duct is being connected to a 26x22 RA duct. |
02/18/2010 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
02/18/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the locations where keynotes 60 and 61 occur. Are the noted water heaters the same as WH-1 and WH-2? Water heaters WH-1 and WH-2 are specified as electric, not gas on sheet P3.1. 2. Provide revised gas piping notes reflecting the new total gas load; the total gas load (keynote 37) doesn't agree with the identified loads. 3. How is combustion air being provided for the water heaters? |