Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM02154
Parcel: 129020470

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02154
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2009 GERRY KOZIOL WWM REVIEW Approved
09/29/2009 MARTIN BROWN FIRE REVIEW Denied Note on cover sheet refers to a 13R sprinkler system. This is only allowed in RESIDENTIAL occupancies.
Also, please include the following fire sprinkler design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
10/02/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/02/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
10/05/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide structural calculations and details to show that the Type I and Type II hoods are supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
2. Comment not resolved. Show that the range installation complies with the manufacturer's listing for clearances from combustibles. Note that elevation 7/A2.0 shows combustible cabinets located adjacent to the commercial cooking appliance.
10/05/2009 ROBERT SHERRY WATER REVIEW Approved Tucson Water limits a 1-1/2" meter to a maximum demand of 50 GPM. Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project (54 GPM). Reference: Sections 610.2 and 610.12, UPC 2006.
(9/29/09 - Tucson Water confirmed that the existing water meter is actually 2")
10/05/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2009 DELMA ROBEY OUT TO CUSTOMER Completed
10/06/2009 SUE REEVES REJECT SHELF Completed