Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02154
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/29/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/29/2009 | MARTIN BROWN | FIRE | REVIEW | Denied | Note on cover sheet refers to a 13R sprinkler system. This is only allowed in RESIDENTIAL occupancies. Also, please include the following fire sprinkler design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. |
10/02/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/02/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
10/05/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide structural calculations and details to show that the Type I and Type II hoods are supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006. 2. Comment not resolved. Show that the range installation complies with the manufacturer's listing for clearances from combustibles. Note that elevation 7/A2.0 shows combustible cabinets located adjacent to the commercial cooking appliance. |
10/05/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | Tucson Water limits a 1-1/2" meter to a maximum demand of 50 GPM. Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project (54 GPM). Reference: Sections 610.2 and 610.12, UPC 2006. (9/29/09 - Tucson Water confirmed that the existing water meter is actually 2") |
10/05/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/06/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
10/06/2009 | SUE REEVES | REJECT SHELF | Completed |