Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM02154
Parcel: 129020470

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02154
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2009 DAVE MANN FIRE REVIEW Denied Rated corridors are required by IFC 1017. Provide cross sections and detail for walls, doors, connections to structure, and fire dampers for wall or ceiling penetrations.

Provide an area calculation for the building.
08/27/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G0.0; INDEX TO DRAWINGS: THE INDEX DOES NOT INCLUDE ALL SHEETS IN THE SET. REVISE.
2. SHEET G0.0; GOVERNING CODES: REMOVE REFERENCE TO THE 1994 ADAAG. NOT USED FOR THIS PROJECT.
3. SHEET G0.0; CODE REVIEW: THE ALLOWABLE BUILDING AREA IS MET BY SEPARATING THE BUILDING INTO AREA ONE (3632 SF) AND AREA TWO (8893 SF). IT IS NOT CLEAR ON THE DRAWINGS WHERE AREA ONE AND TWO ARE LOCATED. PROVIDE CLARIFICATION ON THE PLAN.
4. SHEET G0.0; CODE REVIEW: IN ORDER TO TREAT AREAS ONE AND TWO AS SEPARATE SPACES, THEY MUST BE SEPARATED BY A FIRE WALL PER THE IBC SECTION 705 AND TABLE 705.4. PROVIDE THIS ANALYSIS AND INDICATE THE WALL CONSTRUCTION ON THE PLANS.
5. SHEET A2.0; ELEVATION 5: KEYNOTE 2 IS INCORRECT. REVISE.
6. SHEET A2.0: SHOW THE REQUIREMENTS OF IBC SECTION 1109.11 FOR ACCESSIBLE COUNTERS AND WORK SURFACES ARE MET BY PROVIDING COUNTER HEIGHTS ON THE ELEVATIONS.
7. GENERAL: NO STRUCTURAL CALCULATIONS WERE INCLUDED WITH THE PROJECT DRAWINGS. THE STRUCTURAL PORTION OF THE PROJECT WAS NOT REVIEWED AT THIS TIME.
8. GENERAL: PROVIDE A PROJECT COST BREAKDOWN ON THE PLANS, INCLUDING THE MAXIMUM 20% FOR ACCESSIBILITY PER IBC SECTION 3409.7.
9. GENERAL: FOLLOW THE REQUIREMENTS OF IBC SECTION 3409.6 FOR ALTERATIONS TO EXISTING BUILDINGS. PROVIDE VERBAGE ON THE PLANS AS TO THE EXTENT OF ACCESSIBLE ALTERATIONS.
10. GENERAL: FOLLOW THE REQUIREMENTS OF IBC SECTION 1109.5 FOR ACCESSIBLE DRINKING FOUNTAINS, AND INDICATE ON THE PLANS HOW THIS IS ADDRESSED. A SINGLE POINT OF USE WATER DISPENSER MAY BE USED IN LIEU OF A HIGH/LOW FOUNTAIN.
11. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL COMMENTS.
08/28/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
09/01/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify which code is to be used. Code analysis data sheet lists 2006 UPC to be used, plan cover sheet lists 2006 IPC to be used. Note that if the IPC is to be used, a petition of appeal from the building official will be required. 2. Include all plumbing sheets in the plan as referenced in the demo notes, key notes, and general notes.
09/01/2009 RMYERS1 WATER REVIEW Denied 1. Provide information on the plan that shows domestic water supplied to this site.
09/08/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the operating weights for the new rooftop AC units with the structural engineer. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006.
2. Provide structural calculations and details to show that the Type I and Type II hoods are supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
3. Show that the hood installation complies with Section 507.9, IMC 2006 for clearances. Note that elevation 7/A2.0 incorrectly shows the stainless steel backsplash terminating less than 18" from the edge of the hood and combustible cabinets located less than 18" from the commercial cooking appliance.
4. A Type II hood is designed for use over cooking or dishwashing operations that produce only heat or moisture. Clarify what operations will be occurring under the proposed Type II hood in the Mannequin Cleaning and Storage Room. Provide a listing of the type and quantities of any chemicals that will be used in the cleaning operation to determine the occupancy type. Reference: Sections 106.3.1 and 502.1, IMC 2006.
5. Show that the Type I hood complies with Section 507.2.1.1, IMC 2006.
6. Show that adequate make up air is being provided for the kitchen exhaust hood. Reference: Section 508.1 IMC 2006.
7. Show that adequate make up air is being provided for the exhaust hood in the Mannequin Cleaning and Storage Room. Reference: Section 508.1 IMC 2006.
8. Clarify how the return air system is configured for the existing A/C units, (e.g. ducted or return air plenum; use of the hallway as a duct).
09/10/2009 GERRY KOZIOL WWM REVIEW Denied need plumbing drawings for review. not included with set
09/17/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2009 DELMA ROBEY OUT TO CUSTOMER Completed