Permit Number: T09CM02125
Parcel: 12620001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02125
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2009 RONALD BROWN ADA REVIEW Approved
09/11/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/22/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Ventilation air for the restrooms may be transferred from other building spaces provided that sufficient ventilation air is being supplied to those spaces. How much ventilation air is being supplied to hall 103? Reference: Sections 403.2.2 and 403.3, IMC 2006.
2. Comment not resolved. The area used to calculate the required ventilation rate is the net floor area: footnote a, Table 403.3, IMC 2006. The occupied zone referred to in Section 403.1 is the area into which the air is to be delivered; the area of the occupied zone is not used to calculate the required ventilation rate. The common ventilation system calculations shown on the revised sheet M1.0 are correctly done but with incorrect input. Reference: Sections 403.1, 403.3, and 403.3.2, IMC 2006.
09/23/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. Section 1101.11.2.1, UPC 2006 requires the minimum scupper width to be equal to the circumference of the roof drain required by Table 11-1, UPC 2006; a 2" roof drain has a circumference of approximately 6-1/4" and the 3" roof drain required for roof section C has a circumference of approximately 9-1/2".
09/28/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
10/01/2009 SUE REEVES REJECT SHELF Completed