Permit Number: T09CM02112
Parcel: 132161260

Address:
4821 S CALLE OLE

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02112
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM02112
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
" Provide manufacturer specification sheets for the distribution switch and battery system.
" Show the charge controller model number with exterior cabinet on the plans.
" Show equipment (charger max #6) with conductor size rating compatible with the battery system conductors (4/0 cu), R106.1.1.

STRUCTURAL PLANS:
1. The rafter lengths provided (14' & 16' span roof areas) are undersized for supporting the additional dead load, R301.1 & Table R802.5.1. Provide a design for supporting the required collector panel dead load along with a 20 PSF live load.
2. Show the battery enclosure specifications or method of construction with ventilation as required for selected batteries.
NOTES / SPECIFICATIONS
1. Provide the exact wording for the DC Power Source "Vmax" marking (note #3) for the calculated maximum system voltage rather than the component maximum rating of 600V, NEC 690.53.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review