Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T09CM02107
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Need structural evaluation of HVAC unit trade out |
| 08/06/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical denied see comments for T09CM02105 |
| 08/06/2009 | JASON GREEN | ENGINEERING | REVIEW | Passed | |
| 08/06/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the SEER for the proposed split system A/C unit. 2. Verify that the existing duct insulation has a vapor barrier. 3. Explain how the condensate will be handled. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/13/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |